Servo - subtilitas/rcbench GitHub Wiki

Servo procedures

English · Deutsch

Three procedures on a servo. The first measures a servo as installed: the limit search runs on the SERVO screen and reads INA3221 CH1, and for a KST or Chaservo servo on the programming port it can lower the servo's own travel limits. The second, the synchroniser, needs a current sensor across a pair of outputs, which is not fitted, and runs against a modelled servo only. Their defaults are from servo_limit_defaults() and servo_sync_defaults() in shared/servo/. The third, the automatic test, reads the current of the supply that feeds the servo.

Installed mechanical limit

Purpose

Endpoints set in a transmitter are estimates. A servo held against a mechanical stop draws stall current for as long as it is commanded there, and the installation, not the servo, determines where the stop is. The two ends of a surface's travel differ; measure both.

Method

The search steps outward from centre in 10 µs of pulse width per step (about 0.9° on a servo with 11 µs per degree of travel), up to 600 µs from centre and never past 500 or 2500 µs. A last step shorter than 10 µs reaches that end, so the end itself is measured. After each step it waits 120 ms for the servo to settle and averages the current over 80 ms. While the surface moves freely the current is flat and low. The linkage counts as bound when the current exceeds 1.8 times the free-running baseline and exceeds it by at least 0.15 A. The search stops at the first such step, backs off 25 µs, and reports that pulse width as the endpoint.

On the bench the limit run (shared/servo/servo_limrun.c) searches the low side first, then the high side. Where depends on the target:

PWM TARGET Read first Search
a SERVO PWM pin on OUTPUTS nothing PULSE CENTRE out to PULSE MIN and PULSE MAX
PROG PORT a read session of the programmer the servo's NEUTRAL out to its own PULSE LOWER and PULSE UPPER, never past them

The distance to that end replaces the 600 µs. The current is INA3221 CH1's 50 ms windows, so each position takes 250 ms. The servo is held at the centre for 1000 ms before each search and after it: the return from an end, 600 µs at 0.67 µs/ms, takes 900 ms, and the baseline is not to see it.

Duration: the host test holds a full search against the modelled servo to under 12 s. A run on the bench is not measured.

Running it

The LIMITS page of the SERVO screen's settings holds the run. LIMIT RUN chooses SEARCH ONLY or SEARCH+PROG with a tap. SERVO PULSES, shown with PWM TARGET on PROG PORT only, chooses KEEP or 1000-2000 with a tap; it starts at KEEP. START LIMIT RUN starts the run with a 2 s hold, as START TEST does; a tap or a shorter hold starts nothing.

The limit run, ready

The line under the button names what the run drives and reads, the whole time: OUTPUT PROG PORT GP13, CURRENT INA3221 CH1, or the GPIOs bound as SERVO PWM with PWM TARGET on OUTPUTS. While the run goes on, the left card shows its box: the phase, the side and the pulse commanded, and the output again on its third line. The right card's TARGET row stays in sight as well.

The limit run, programming

The run reads the INA3221 and nothing else. The PD mini's readings and the panel's model are refused before anything is driven: the button stays grey and the line under it says why.

Line Condition
ARM FIRST the bench is SAFE
LAST REPORT STILL WRITING an automatic test or a limit run is under way, or its report is still going to the card
INA3221 NOT SET UP AS THE SERVO RAIL'S METER INA3221 or its CH1 off in SETUP, a coprocessor older than protocol 4.11, or a SENSE page that does not hold the set-up
INA3221 NOT ONLINE no link, the part not answering, or its reset count moved
NO INA3221 WINDOWS YET the INA3221 is not the servo rail's meter yet: its set-up held for less than 1000 ms, or no window with current in the last 200 ms
SERVO RAIL UNDER 3.0 V OR NOT READ the last INA3221 window holds no rail voltage, or its mean is under 3.0 V (SERVO_LIMRUN_RAIL_MIN_MV). An output that is off reads 0 V, and a search there would find two free ends on a servo that never moved. 3.0 V lies under the 4.8 V servos are commonly specified from, so a single lithium cell's rail still starts; the voltage a given servo stops moving at is not measured
PORT PWM OFF: THE PORT RENDERS NO PULSE PWM TARGET on PROG PORT with PORT PWM off
NO SERVO PWM PIN, PINS NOT READ PWM TARGET on the bench's outputs with no output bound as SERVO PWM, or the binding not read yet: the TARGET row's own words
CENTRE NOT BETWEEN PULSE MIN AND MAX PULSE CENTRE is not between PULSE MIN and PULSE MAX

Programming the servo's travel limits

SEARCH+PROG is offered for a servo on the programming port: PWM TARGET on PROG PORT, the port in PWM, and a supply of 4.8 V or more. With a PD mini answering, its output must be on and its set point counts; without one, the servo rail's mean in the INA3221's last window. On the bench's outputs the run searches only, the row reads SEARCH ONLY, and the third line reads PROGRAMMING: ONLY A SERVO ON THE PROG PORT. On PROG PORT every run starts with a read session, so the other conditions stop SEARCH ONLY as well: the button stays grey and the third line names the condition.

Line Condition
PROGRAMMING: THE PORT IS NOT IN PWM the programmer holds the port, or the port is not ready for a run
PROGRAMMING: PD MINI OUTPUT OFF a PD mini answers with its output off: the read session would switch it on beside the supply that feeds the rail
PROGRAMMING: SUPPLY SET BELOW 4.8 V a PD mini answers and its set point is under 4.8 V
PROGRAMMING: SERVO RAIL BELOW 4.8 V no PD mini answers, and the servo rail in the INA3221's last window is under 4.8 V or not read

The read first

Every run on PROG PORT, SEARCH ONLY as well, starts with a read session. The servo is held at PULSE CENTRE, the run switches the bench to SAFE, CONNECT reads every register, LEAVE gives the port back, and the run switches the bench to ARMED. Nothing is driven before that.

  • A read that fails ends the run before any search: ABORTED, programming port did not finish, where CONNECT or its read does not complete; FAIL, no KST or Chaservo servo read, where the servo read holds values the hard rules do not take. A servo that is no KST or Chaservo is searched with PWM TARGET on a SERVO PWM pin.
  • NEUTRAL not between PULSE LOWER and PULSE UPPER ends it as FAIL, NEUTRAL outside LOWER/UPPER.
  • PULSE LOWER to PULSE UPPER not inside the bench's PULSE MIN to PULSE MAX ends it as FAIL, servo pulses outside MIN/MAX. The bench stays SAFE, nothing is driven, and the box and the report name both ranges, for example 900-2100 NOT IN 1000-2000 us.

A KST servo as delivered holds PULSE LOWER 900.0 µs and PULSE UPPER 2100.0 µs. The STANDARD PWM type's PULSE MIN and PULSE MAX are 1000 µs and 2000 µs, so that servo is refused at KEEP. SERVO PULSES at 1000-2000, or a PWM type with a range that holds 900 to 2100 µs, lets it run.

SERVO PULSES at 1000-2000 writes PULSE LOWER 1000.0 µs and PULSE UPPER 2000.0 µs in the read session, before anything is driven, and reads them back. NEUTRAL is not written. A servo that holds those values already gets no write. NEUTRAL outside the new range ends the run as FAIL before anything is driven, with RESTORE offered. The setting works with SEARCH ONLY and with SEARCH+PROG; with SEARCH ONLY the pulses are the only write, and the third line says SEARCH ONLY: SETS PULSE LOWER/UPPER, NOTHING ELSE.

The registers and the model

LEFT ANGLE and RIGHT ANGLE are the servo's own travel limits, one 8-bit register each, in a unit that is not known. The smallest value the programmer's hard rules take is 1 on a KST: 0 is refused. A value under 50 is a soft limit; the run's 2 s hold is the consent to it.

The run takes the servo as linear. PULSE LOWER and PULSE UPPER are the input pulses at which the servo reaches the full travel that LEFT ANGLE and RIGHT ANGLE set. Between NEUTRAL and that pulse the travel is linear in the pulse; past it the servo holds full travel. The share of a side at pulse p is

f = (p - NEUTRAL) / (P_lim - NEUTRAL)

with P_lim PULSE LOWER on the low side and PULSE UPPER on the high side, as the servo holds them when the search runs. The unit of LEFT ANGLE and RIGHT ANGLE is not known, and the linear relation is an assumption, not a measurement. A bound side whose last free pulse is not past NEUTRAL ends the run as FAIL, free end not past NEUTRAL, before any write.

Two writes a bound side

v0 is the value the side's register holds at the read.

  1. The overset: v1 = ceil(v0 x fb x 1.03), fb the share at the first search's first bound pulse, at most v0 and at least the smallest value. The first bound pulse lies at or past the stop, so at v1 the stop stays reachable and moves close to the pulse limit. The side is searched again. Free there, the run ends as FAIL, no stop after the overset write, with no second write and RESTORE offered.
  2. The final value: v2 = floor(v1 x f1), f1 the share at the overset search's last free pulse, at least the smallest value. No margin is added: the last free pulse lies one 10 µs step short of the bound one. An overset search that binds far inside the pulse limit still gives v2 this way; no further overset follows.

Worked, on the host's modelled servo: NEUTRAL 1500.2 µs, PULSE LOWER 900.0 µs, v0 150, the stop at 1000 µs. The first search is free at 1000 µs and bound at 990 µs: fb = 510.2 / 600.2 = 0.850, v1 = ceil(150 x 0.850 x 1.03) = 132. At 132 the search is free out to 930 µs: f1 = 570.2 / 600.2 = 0.950, v2 = floor(132 x 0.950) = 125. At 125 the full travel ends at 1000.2 µs.

The overset is left out where v1 would not lie below v0, or where the model moves the stop less than 20 µs: d0 x (v0 - v1) / v1 under 20 µs, d0 the first search's last free pulse's distance from NEUTRAL. A search could not tell that move from none. The first search then counts as the overset's, and v2 = floor(v0 x f0), f0 the share at its last free pulse: one write for that side.

Which register limits which side

The protocol notes do not say which pulse side each register limits, nor how REVERSION changes that. The run finds it on the first bound side's first write: that value goes to LEFT ANGLE alone (RIGHT ANGLE where LEFT ANGLE holds the smallest value already), and the side is searched. The end moved when it is free now or its endpoint lies 20 µs further out. An end within 20 µs of where it was sends LEFT ANGLE back to its value and the value, worked out again from RIGHT ANGLE's v0, to RIGHT ANGLE; moved then, RIGHT ANGLE limits that side. An end that stays with both registers tried ends the run as FAIL, LEFT/RIGHT ANGLE side not found. An end that moved inward by 20 µs or more ends it as FAIL too. An end that binds with its register at the smallest value ends it as FAIL, binds at the smallest angle. A register whose side never bound keeps its value.

Last, both ends are searched again: PASS when both are free, FAIL an end binds after programming when either binds. No further write follows a FAIL; RESTORE gives the values before the run back.

Sessions

The run writes in sessions of the programmer:

  1. The servo goes back to the centre and is held there for 1000 ms.
  2. The run switches the bench to SAFE.
  3. CONNECT takes the port and reads every register.
  4. The write: ENABLE WRITE TO SERVO on, the run's fields, the write switch off again. The write is the programmer's ordinary write with every limit check, and reads the values back.
  5. LEAVE gives the port back to PWM.
  6. The run switches the bench to ARMED and searches the side the write was for.

The read session writes nothing but the pulses of SERVO PULSES. A LEAVE this link or supply does not complete ends the run before any value changes. The first write of the run saves the servo's values to a backup file on the card, as the programmer's first write does; the later sessions save none. Each later session reads the servo again. Another type, REVERSION switched, another range of values the hard rules take, other pulses, or LEFT ANGLE and RIGHT ANGLE other than the run last wrote end the run as ABORTED, servo holds other values, before it writes again.

Constant Value Purpose
SERVO_LIMRUN_WRITES_MAX 8 register values a run writes at most: PULSE LOWER and PULSE UPPER (2), the overset and the final value on each side (4), and LEFT ANGLE's first write with its value back when RIGHT ANGLE limits that side (2). A session whose values would pass it is not sent: FAIL write cap of 8 values reached
SERVO_LIMRUN_OVERSET_PCT 3 % the overset above the share at the first bound pulse
SERVO_LIMRUN_STD_LOWER_DUS, SERVO_LIMRUN_STD_UPPER_DUS 1000.0 µs, 2000.0 µs what SERVO PULSES at 1000-2000 writes
SERVO_LIMRUN_MOVED_US 20 µs an end that moved, or stayed; the smallest stop move an overset is written for
SERVO_LIMRUN_RETURN_MS 1000 ms at the centre before each search and before each SAFE

Writes: no step of the protocol is known to make a value permanent, and no write that changes RAM only is known. Every write is the register write the programmer reads back. Whether a KST servo keeps the value in EEPROM (electrically erasable programmable read-only memory) at every write, and how many writes that memory takes, is not known; the cap keeps a run to 8 values. A run with both ends bound and SERVO PULSES at 1000-2000 on the host's modelled servo wrote 6 values in 4 writes and 4 sessions, 85.6 s, with REVERSION OFF, and 8 values in 5 writes and 5 sessions, 97.7 s, with REVERSION ON.

The ends found are not applied to the bench's own PULSE MIN and PULSE MAX.

Protections

Protection Value Effect
Current ceiling 3.0 A abort, checked at every 1 ms sample of a window
The INA3221 at the end of its range a clipped sample abort
Stall timeout window means above 1.0 A for 400 ms abort
No window 200 ms, 4 windows of 50 ms abort; SERVO_TEST_WIN_STALE_MS, the automatic test's figure. A window without a current reading does not count as a window
One search 40 s abort: 1000 µs of travel is 100 positions of 250 ms, 25 s
One programmer step 150 s abort: CONNECT with its read, a write or LEAVE
The bench switching 3 s abort when SAFE or ARMED is not in place 3 s after the run asked
The supply set points and output, on or off, as at its first reading, answering or not, in every phase but the programmer's sessions (CONNECT to LEAVE), which own the supply; an output off at the start and switched on, or a supply that did not answer at the start and answers later, its output on or off, ends the run as supply or rail voltage changed, so no second supply is switched on beside a rail fed from elsewhere; a CONNECT is not sent while a PD mini answers that the run did not start with, or one whose output is off: the run ends as a reading outside a session ends it, supply or rail voltage changed for a PD mini the run did not start with and supply output went off for its own; during a search also the rail within 1.0 V of the first window abort
The rail voltage in a search's window present in every window of a search, its mean at 3.0 V or more (SERVO_LIMRUN_RAIL_MIN_MV), the first window included abort before the window moves the search: no rail voltage in a window without a reading, supply or rail voltage changed under 3.0 V; the 1.0 V band's reference is the run's first window, which holds the rail
Step size 10 µs one step cannot move the horn from free to hard against the stop

These hold in every phase. The search and the protections read the current's magnitude: a shunt fitted the other way round reads a bound servo as a more negative current, and the run finds it as it does with the shunt the right way round. A reading of -32768 mA counts as 32768 mA, past the 3.0 A ceiling. The run follows the arming rules of the SERVO screen and the programming port: its ARM is refused while the port is held, a STOP latch or lost touch events keep the bench SAFE, and an ARM that does not land ends the run.

The synchroniser is a module in shared/servo, tested on the host against a modelled servo; neither firmware image calls it.

What ends a limit run

STOP, STOP RUN on the box or the LIMITS page, a switch to SAFE by the operator, link loss, leaving the screen, the operator taking the servo, a change to the servo's settings, lost touch events, the INA3221 no longer the meter, and a supply that stops answering, trips, switches off or has its set points changed: the reasons of the automatic test, in What ends a run. The run's own SAFE and ARM end nothing. Each ends the run as ABORTED with the output off and the servo released. A run that ends while it waits for ARMED also asks SAFE: an ARM it asked that the bench has not taken yet does not arm the bench after the end. A start of the panel clears the run without a report.

The values last written stay in the servo. A run that wrote and did not pass says RESTORE IN PROGRAM on its box. A write that fails once sent, with no answer or an answer the programmer does not take, counts as written: part of it may have landed. A write the programmer refuses before it is sent counts as none. RESTORE on the programmer, after CONNECT and READ ALL, offers Values before the limit run: the servo as the run's first session read it, written back as an ordinary write of LEFT ANGLE, RIGHT ANGLE, PULSE LOWER and PULSE UPPER. It is offered while the servo read differs from it in those four fields and in no other. The hold is in the panel's memory: a start of the panel forgets it, and the backup file on the card remains. A session after the run is the operator's: its first write saves its own backup file.

A run stopped after a write RESTORE after a limit run

Results

  • An endpoint is reported already backed off by 25 µs.
  • "No limit found" (FREE) means the search measured the end of its travel without binding: PULSE MIN or PULSE MAX on a SERVO PWM pin, the servo's PULSE LOWER or PULSE UPPER on PROG PORT.
  • A limit close to centre may be a tight spot in the linkage, such as a binding bellcrank or a rubbing pushrod, rather than the end of travel.
Verdict Meaning
FOUND search only: an end binds; the endpoints are reported
FREE neither end binds; nothing is written
PASS programmed, and both ends free in the last search
FAIL the run ended as planned and an end still binds, or the servo cannot be programmed
ABORTED a protection, the operator, the link, the meter, the supply or the programmer ended it

The box on the left card shows the verdict, the reason or the values (LEFT 150>87 RIGHT 150>95), the ends or the output the run started on, and the report's file name until CLOSE.

A programmed servo Search only The servo's pulses outside PULSE MIN and PULSE MAX

The report is a BENCHnnn.TXT of its own, with no CSV file beside it, under the next free number, written whatever the DUT page's REPORT says. During a run neither the bench log nor the supply log writes a row; the supply log's time runs on through the run, as its totals do. From the run's start until the card has closed the report it counts as an open log run: Wi-Fi and an update wait for it, as for a run's CSV. A run on the host's modelled servo with REVERSION OFF and SERVO PULSES at 1000-2000; the stops at 1150 µs and 1880 µs of horn travel lie at 1208 µs and 1817 µs of input pulse once PULSE LOWER and PULSE UPPER are 1000.0 µs and 2000.0 µs:

RCBENCH SERVO LIMIT REPORT
Result:         PASS
Device:         SERVO
Firmware:       rcbench 0.20.0
Mode:           search, then LEFT ANGLE and RIGHT ANGLE programmed
Output:         PROG PORT GP13, 50 Hz
Pulse range:    centre 1500 us, 1000-2000 us
Searched:       from 1500 us out to 1000 us and 2000 us
Current:        INA3221 CH1, 50 ms windows, shunt 100.0 mOhm
Search rule:    10 us steps, settle 120 ms, mean of 80 ms; bound above 1.8 x free and +0.15 A
Protections:    a sample at 3.0 A, above 1.0 A for 400 ms, no window for 200 ms, 40 s a search
Duration:       85.6 s
AS5600:         not fitted, no angles

ENDS (the search before programming)
Low end:        bound at 1200 us, endpoint 1235 us; free 0.120 A, bound 0.627 A
High end:       bound at 1820 us, endpoint 1785 us; free 0.120 A, bound 0.322 A

PROGRAMMING (LEFT ANGLE and RIGHT ANGLE, unit not known)
Servo:          type 6, REVERSION OFF
Servo pulses:   NEUTRAL 1500.2 us, PULSE LOWER 900.0 us, PULSE UPPER 2100.0 us
Pulse write:    PULSE LOWER 900.0 -> 1000.0 us, PULSE UPPER 2100.0 -> 2000.0 us
LEFT ANGLE:     150 before, 87 after; limits the low end
                share free 0.580, bound 0.600; overset 93, share 0.940; final 87
RIGHT ANGLE:    150 before, 95 after; limits the high end
                share free 0.620, bound 0.640; overset 99, share 0.960; final 95
Method:         linear in the pulse; overset +3 % on the share at the first bound pulse, then the share its search found free
Writes:         values written 6, writes sent 4, cap 8 values; sessions 4
Backup:         KST001, the values before the run

ENDS AFTER PROGRAMMING (both searched again)
Low end:        free to 1000 us; free 0.120 A
High end:       free to 2000 us; free 0.120 A

Unit: the unit of LEFT ANGLE and RIGHT ANGLE is not known; the travel is taken as linear in the pulse from NEUTRAL to PULSE LOWER and PULSE UPPER, which is not measured.
Bench: the ends found are not applied to PULSE MIN and PULSE MAX.

With the AS5600 fitted, each end has a line with the horn's angle at its last free position, AS5600 +38.5 deg at the last free position. A run that wrote and did not pass has a Restore: line. A run that sent no write has no Backup: line: the values before the run are held from the first write on. The Backup: line names the file this run's first write saved, also when that write was sent and lost, never an earlier run's file. The Searched: line names the search's centre and ends; a run that ended before its first search has none. A run on a SERVO PWM pin has no Servo pulses: line.

Not measured: every figure above on a real servo. The unit of LEFT ANGLE and RIGHT ANGLE, which register limits which pulse side on a real KST or Chaservo servo, whether a written value persists through a power cycle, whether the servo moves when its limit is written, the time a session takes on hardware, and the time from LEAVE to a working ARM are not known.

Synchronising two servos on one surface

Purpose

Two servos on one surface (dual ailerons, split elevator) work against each other whenever their travel or their centre disagree, and draw extra current continuously. The surface shows no visible sign.

Method

The two stop working against each other at the point of minimum total current. The search holds servo A and sweeps a correction on servo B, at centre and at ±300 µs deflection:

  • a difference at centre is an offset error (trim);
  • a difference at an end is a travel error for that end.

Each stage runs 3 scans of 7 points. The first scan covers ±40 µs around the stage's start point: 0 µs for the centre stage, the ±300 µs deflection for the end stages. Each later scan is centred on the best point of the scan before and covers ±13 µs, then ±4 µs. Each point waits 120 ms plus the travel time at an assumed 0.8 µs/ms, then averages the current over 100 ms. A minimum is accepted when the current varies by at least 0.08 A across the scan. The current ceiling is 4.0 A for the pair.

Each end gets its own correction; a linkage with a horn and a pushrod is not symmetric about centre. One current sensor across the pair is sufficient.

Results

  • A pair that is already synchronised produces a minimum at zero correction.
  • "No minimum" means the current varied by less than 0.08 A across the widest scan.
  • Two servos that agree with each other and are both wrong produce no difference in current. That case needs the accelerometer or inspection.

Automatic test

Purpose

What a servo draws at rest, moving and holding an end, and how long it takes from end to end, at the supply voltages it is rated for; and the voltage below which it no longer moves (brown-out). Nothing on the bench measures the horn unless the output encoder is on (see below), so every result is read from the current of the supply that feeds the servo: the PD mini (WeAct PD Power Mini V1) when SETUP INTERFACES enables it, the panel's supply model otherwise. A run on the model says so in its report, and its numbers are simulated. While the INA3221 is the servo rail's meter at START TEST and the supply is the PD mini, the run reads the INA3221's CH1 instead, in 50 ms windows: see The meter.

START TEST on the SERVO screen's TEST page starts it: Screens describes the controls. The engine is shared/servo/servo_test.c; the constants below are in servo_test.h.

Method

The voltage steps are the TEST page's STEP 4.8 V and STEP 6.0 V, and with HV SERVO on, STEP 7.4 V and STEP 8.4 V. HV SERVO is off at every restart. A run with a step above 6.0 V starts only through the HV SERVOS ONLY warning held for 2 s. The current limit through the run is the one on the SET line.

Each step runs these phases:

Phase The servo Ends
SET at PULSE CENTRE; the voltage asked; the first step switches the output on the supply reads the set point back within 0.05 V, at most 3000 ms
SETTLE at PULSE CENTRE after the TEST page's SETTLE
IDLE at PULSE CENTRE: the idle current is the mean of the readings, the idle noise their standard deviation after 1000 ms
MOVE a step command to one end, with no slew: SPEED does not apply at the arrival, or after 3000 ms plus the meter's lag (3300 ms on the PD mini): late with movement seen, unseen without
HOLD at that end: the holding current is the mean of the readings after DWELL, at least 600 ms

The two ends are SWEEP's: RANGE of the travel either side of PULSE CENTRE, trim not applied. With the defaults (RANGE 80 %, TRAVEL +/-90 deg, PULSE MIN 1000 us, MAX 2000 us) they are 1100 and 1900 us. CURVE and SPEED shape SWEEP only.

A run that completes also switches the output off and releases the servo to its centre. On a bench it leaves in ARMED, the commanded value shown is then the rest, as after RELEASE: 1500 us for STANDARD PWM whatever the trim, and the next drag or knob turn starts from it. A step's first two moves, centre to the low end and on to the high end, are not counted: they measure each end's holding level. The counted moves then go end to end, MOVEMENTS of them or for TEST TIME, as LENGTH BY says, at most 1000 a step.

  • Threshold: per step, the larger of 0.020 A (SERVO_TEST_MOVE_MIN_A) and 3 (SERVO_TEST_NOISE_K) times the idle noise, the standard deviation of the IDLE readings. The report gives it in the Thresh column. A servo whose readings at rest spread by 0.010 A has a threshold of 0.030 A.
  • Movement: a reading more than the threshold away from the level before the command: above it, or below it when the servo leaves an end it was pushing on.
  • Arrival: after movement, a reading more than the threshold above the destination end's holding level, then the first reading back within 0.05 A (SERVO_TEST_BAND_A) of it, on either side. A reading above the level by the threshold is never an arrival, so the 0.05 A band times no move early where the threshold is smaller. A reading that falls more than 0.05 A below the level instead, as after a burst of current while the servo accelerates, hands the move to the rule below. The two ends' holding levels can differ by more than 0.05 A, so a reading still at the start end's level, or a rising current passing the destination's level, is not an arrival.
  • Arrival at an end held harder than the servo moves, an end pushing on a stop: that level is never passed, so the move has arrived at the first of two readings in a row, after movement, within 0.05 A of the level and of each other. A current that climbs through the destination's level by less than 0.05 A a reading can be taken for an arrival there.
  • Not told apart: a servo whose moving current lies within 0.05 A of the destination's holding current cannot be told from one already there; a move to that end is timed at its first two readings after movement.
  • Window: a move has 3000 ms (SERVO_TEST_TRAVEL_TIMEOUT_MS) plus the meter's lag to arrive: 3300 ms on the PD mini, whose readings show an arrival about 300 ms after it happens. The lag is added rather than the window's last 300 ms left unjudged: a servo arriving at 2900 ms shows it at about 3200 ms and is timed, and a move that never arrives is still late, 300 ms later. A reading at or past the window's end, 3300 ms on the PD mini, is never an arrival: the move is late.
  • Unseen: a counted move with no reading past the threshold within the window. The current cannot tell it from a servo standing still: it is neither timed nor late, and the report counts it in the Unseen column. A step none of whose moves showed movement reads NOT MEASURABLE.
  • Travel time: from the command to the arrival's reading.
  • Moving current: the mean of the readings between the command and the arrival; the peak is the highest of them.

Why the band stays 0.05 A while the threshold scales: replays of the two bench runs below with the band at 0.05 A and with the band equal to the threshold time the same moves to the same millisecond, because a reading above the level by the threshold is never an arrival. The threshold is what had to scale. 0.13.0 took movement to be 0.10 A, and the MG90S moves at 0.04 to 0.077 A over a 0.001 A hold: no move was seen, each ran out at 3000 ms and was counted late, and the run read FAIL.

Limitation: the move to the centre can reach IDLE. With SETTLE at 500 ms the IDLE readings can still carry the end of the step's move to the centre: 0.025 A falling to 0.003 A on the 1102HB at 5.00 V, from the PD mini's 0.3 s lag and the move itself. That raises the idle mean and the noise, and the threshold with it: 0.026 A there instead of 0.020 A. A longer SETTLE avoids it.

Brown-out. After the steps, with BROWN-OUT on: from 5.00 V (SERVO_TEST_BROWNOUT_START_V), or the voltage cap in force if lower, down in 0.20 V steps (SERVO_TEST_BROWNOUT_STEP_V) to 3.00 V (SERVO_TEST_BROWNOUT_FLOOR_V), or the supply's lowest set point if higher. The cap in force is the lowest of VOLTAGE MAX, the supply's own maximum, and for the PD mini its input voltage less 0.7 V. A floor off the 0.20 V grid is the last step: on the model, whose lowest set point is 3.3 V, the walk goes 5.0, 4.8 ... 3.4, 3.3 V. Each voltage runs SET, SETTLE and IDLE, then two moves (SERVO_TEST_BROWNOUT_MOVES), centre to the high end and on to the low end, each held 600 ms. A voltage shows no movement when no reading of either move lies more than that voltage's threshold, from its own IDLE readings, from the level before its command. The walk stops at the first voltage with no movement; the report gives that voltage, the lowest one the servo moved at, and the threshold at the last voltage run. No movement at the first voltage, 5.00 V, reads not measurable: a servo that never showed movement may move under the threshold.

Constant Value What it is
SERVO_TEST_MOVE_MIN_A 0.020 A the smallest threshold: movement; above the destination's level, not there yet
SERVO_TEST_NOISE_K 3 the threshold in idle noises, where that is larger
SERVO_TEST_BAND_A 0.05 A arrived at the holding level
SERVO_TEST_PDMINI_LAG_MS 300 ms the PD mini's lag, as the report states it
SERVO_TEST_IDLE_MS 1000 ms the idle measurement
SERVO_TEST_HOLD_MIN_MS 600 ms the shortest hold measured
SERVO_TEST_TRAVEL_TIMEOUT_MS 3000 ms a move that has not arrived is late, after this plus the meter's lag
SERVO_TEST_SET_TOL_V 0.05 V a set point read back
SERVO_TEST_SET_TIMEOUT_MS 3000 ms for the set point, and for the output to come on
SERVO_TEST_STALE_MS 1500 ms no new reading ends the run
SERVO_TEST_STALL_ABORT_MS 1000 ms above STALL AT this long ends the run
SERVO_TEST_CC_ABORT_MS 1000 ms the supply in constant current this long ends the run
SERVO_TEST_WIN_STALE_MS 200 ms a run on the INA3221: no window this long ends it; 4 windows of 50 ms. The limit run shares it
SERVO_TEST_WIN_MS 50 ms one window of the INA3221
SERVO_TEST_NEG_IDLE_A 0.020 A an idle current below minus this is reported as the shunt's direction
SERVO_TEST_BROWNOUT_START_V 5.00 V where the brown-out walk starts
SERVO_TEST_BROWNOUT_STEP_V 0.20 V each step down
SERVO_TEST_BROWNOUT_FLOOR_V 3.00 V the lowest voltage asked
SERVO_TEST_BROWNOUT_MOVES 2 moves at each brown-out voltage

Time resolution

A reading counts once. For the PD mini the count is the SUPPLY page's SAMPLES register: the coprocessor's count of the module's output readings that answered. A page read whose SAMPLES has not moved brings no new reading, whatever voltage and current it carries -- a display read on the coprocessor that was slow (up to 400 ms, PDMINI_REPLY_MS) or failed leaves the last ones standing -- and a run with no new reading for 1.5 s ends. A reading is stamped with the panel's time of the first page read that showed its count; the model counts and stamps its own steps. The coprocessor reads the PD mini's output every 100 ms (PDMINI_DISPLAY_MS) and the panel reads the page every 100 ms (SUPPLY_LINK_READ_MS), so a new reading reaches the test every 100 ms at best; the model gives one every 50 ms. When SAMPLES steps by more than one between two page reads, the readings in between never reach the test: the report counts them on its Skipped line, and the rate taken by the supply includes them. The report states both rates as measured during the run, and the mean interval between two readings that reached the test.

A travel time ends at the first reading back at the holding level, so it is late by up to one interval. It also holds the command's way from the panel to the pin: render loop, control task, CAN (Controller Area Network) link and the next PWM (pulse-width modulation) frame. That delay is not measured. How the PD mini averages a reading is not known.

The PD mini's readings lag and repeat. Two runs on the bench with the PD mini on 0.13.0, an MG90S and a 1102HB, read it every 102 to 106 ms. The median time from a command to the first reading 0.02 A above the level before it is 0.31 s, and a current often repeats over several readings. Every travel time read off the PD mini is therefore an upper bound: on the MG90S 771 to 989 ms for a servo rated about 0.1 s per 60 deg. The report says so on its Lag, Repeats and Travel times lines, and TRAVEL TIME cannot fail a run on the PD mini: its line gives the longest travel time and reads upper bound, not checked against the limit. What reads the current is described to the run (servo_test_meter_t: a name, the lag, whether readings repeat, whether travel times are an upper bound), so a faster current sensor sets its own and has TRAVEL TIME checked. A run on the panel's model states no lag of its own and checks TRAVEL TIME as the PD mini would: not at all.

On the INA3221 a reading is a window, counted by the window's number: a number that steps by more than one between two windows the run got is counted on the Skipped line. The panel takes each window once and in order; the queue to the screen holds 8, so a frame longer than 400 ms loses the oldest. A window's time is the latest it can have closed: the panel's time of the read that brought it, less 50 ms for each window that closed after it and came in the same read. Windows that arrive together are therefore 50 ms apart in the run and in the CSV, as the ones that arrive one a read are.

The meter

A run reads one meter from START TEST to its end: the servo rail's meter as the panel names it when the run starts (Link).

PD mini INA3221 CH1
The run reads it when the INA3221 is not the rail's meter at START TEST, or the supply is the panel's model the INA3221 is the rail's meter at START TEST and the supply is the PD mini
A reading one reading of the supply, every 102 to 106 ms one 50 ms window of CH1, 20 a second
Current the reading the window's mean. The peak is the window's highest or lowest 1 ms sample, whichever lies further from zero
Voltage the reading at the supply's output CH1's bus voltage at the load side of the shunt: the window's mean in Meas V, its lowest sample in V min
IDLE and HOLD the readings taken in the phase the windows that lie wholly in the phase; one that began before it is in neither. On the host suite's modelled bench IDLE's 1000 ms hold 19 to 20 windows and a hold of 600 ms 11 to 12
MOVE the readings from the command on the windows from the one open at the command on
Travel time to the reading that shows the arrival: late by up to one reading and about 300 ms of lag to the window that shows the arrival: late by up to two windows and the poll that reads them, 145 ms
TRAVEL TIME reported, not checked reported, not checked
A move is late after 3300 ms 3050 ms
The supply's voltage and current every figure and every row not used and not logged
The supply's state: answering, output, trip, set point read back, mode read read

On the INA3221 the panel times a move from the windows. The coprocessor's move capture, which times a move at 1 ms from the PWM frame, is not used by the run.

  • Held to the end. A run on the INA3221 ends ABORTED when the INA3221 stops being the rail's meter, with the condition that failed as its reason (see What ends a run), and when no window reaches it for 200 ms (SERVO_TEST_WIN_STALE_MS). It never goes on with the PD mini: the two meters do not agree. In one recorded run of an MS24 the PD mini's highest reading was 0.390 A and the INA3221's highest 1 ms sample 1.637 A. A run on the PD mini goes on with it when the INA3221 becomes the meter under it.
  • Why not the INA3221. A run on the PD mini with the INA3221 on in SETUP has the report line INA3221: not used: <reason>: the coprocessor is older than link protocol 4.11, the coprocessor does not hold its set-up, it does not answer, no window with current in the last 200 ms, it reset itself, it has worked for less than 1 s, or the supply is the panel's model.
  • Signed current. A negative current is a reading. IDLE CURRENT, HOLD CURRENT, STALL AT and the peak take its magnitude, and the CSV and the report keep the sign. A run whose idle current at any step is below -0.020 A (SERVO_TEST_NEG_IDLE_A) has the report line Current reads negative at rest: shunt direction.
  • Clipping. The INA3221 reads a shunt voltage up to 163.8 mV: 1.638 A on a 0.1 Ω shunt, 3.276 A on 0.05 Ω. A sample at an end of that range counts in its window at the end of the range, and the window is a reading like any other: its mean, its peak and its place in the verdict are the values the part gave. The CSV's clipped column holds the number of such samples in the window, and the report's Clipped line the number of windows with one; their figures are a lower bound. The number of clipped samples in a window decides nothing. A servo that draws more than the range reads the range. Which shunt is fitted decides what this meter can show.
  • The shunt's drop. Meas V and V min are measured behind the shunt. The set point is not raised for the drop: at the end of the range the shunt takes 0.164 V, on any shunt value, and the report's Shunt line says so.

Stall and constant current

Rule Condition Effect
STALL AT a reading after SETTLE on a voltage step whose magnitude is above STALL AT FAIL
STALL AT for 1 s readings above STALL AT for 1000 ms (SERVO_TEST_STALL_ABORT_MS) without one at or under it, in any phase and in the brown-out walk the run ends, above STALL AT for 1 s
Constant current for 1 s the supply reports constant current (CC) in every reading for 1000 ms (SERVO_TEST_CC_ABORT_MS) from the first the run ends, constant current for 1 s, whatever STALL AT is
Constant current for less than 1 s nothing ends and nothing fails; the report's Const. current line gives the number of such readings and the longest stretch from a first to a last
STALL AT at or above the current limit at START TEST the run starts. The TEST page and the report say STALL AT 3.00 A cannot be reached: current limit 2.00 A
STALL AT at or above the INA3221's range at START TEST with the INA3221 as the meter the run starts. The TEST page and the report say STALL AT 2.00 A cannot be reached: INA3221 range 1.638 A
  • Every comparison of a current with IDLE CURRENT, HOLD CURRENT and STALL AT is made in whole mA, in the verdict and in the report alike: a reading of 0.050 A against a limit of 0.05 A passes, and 0.051 A fails.
  • On the PD mini the 1000 ms count from the first reading above STALL AT: a reading 999 ms later leaves the run running, one 1000 ms later ends it.
  • On the INA3221 the reading is the window's mean, whatever its highest sample is, and the 1000 ms count from the start of the first window above STALL AT: 20 windows in a row end the run.
  • A supply in constant current holds its current limit, so no reading lies above a STALL AT at or above that limit. STALL AT and the supply's start current both default to 2.00 A. The constant-current rule ends such a run: a servo on a stop that draws the limit ends it 1.0 to 1.1 s after the supply reports constant current.
  • With the INA3221 on its 0.1 Ω shunt and STALL AT at its default 2.00 A, STALL AT cannot be reached. A servo on a stop that draws less than the supply's limit and more than 1.638 A reads 1.638 A for the whole run; the report then has the Clipped line and the cannot be reached line. STALL AT at 1.60 A or lower, or a shunt of 0.05 Ω, puts STALL AT inside the range.

Not measured: what the PD mini reports with a servo on a stop (constant current or over-current, and whether it switches off by itself), and how long it holds constant current after an inrush. In the recorded MS24 run it held it for 0.43 s twice during healthy moves, at 0.004 to 0.342 A.

The output encoder

An AS5600 magnetic angle sensor on the servo's output shaft, set up under SETUP, INTERFACES, AS5600 (default OFF) and read by the coprocessor (Link, SENSE registers 26 to 31), adds the horn's angle to a run. The current's results are unchanged and the angle decides nothing: it is not part of the verdict and has no limit. Without AS5600 on, the run, its CSV and its report are as without the part. The coprocessor takes the SENSE set-up only while the bank is SAFE. A run uses the angle only when the coprocessor holds AS5600 on: AS5600 switched on while ARMED gives a run without angle columns until the set-up has been taken in a SAFE state.

The angle is the sensor's 12-bit count less the centre count (AS5600 centre, or ENC CENTRE on the DUT page, which takes the live count with the servo at its neutral), in degrees from -180 to just under 180. The sensor counts up in the direction its DIR pin is strapped for; the test assumes the angle rises with the pulse width, so a DIR strap that runs the other way shows as an angle error of twice the travel. Commanded angles are the screen's: -90 degrees at PULSE MIN, +90 at PULSE MAX, with REVERSE and TRIM applied. With REVERSE on, the measured angle is negated the same way, on the screen, in the report and in the CSV, so a horn at the commanded end shows no error. A servo that turns less than 90 degrees over that span shows the difference as angle error.

The count wraps from 4095 to 0, so every angle is a position on one turn and no two are subtracted or averaged as plain numbers. A move's distance from its start is taken the shortest way round, 0 to 180 degrees: two positions 1 count either side of the half turn from the centre are 0.18 degrees apart, not 359.8. A step's end angles at one end are averaged as offsets from the first of them and the mean is put back on the circle, so ends read at +179.9 and -179.9 degrees average to 180 (shown as -180.00), not 0. The angle error is wrapped to -180 to +180 degrees as well.

One turn is all the sensor tells apart, which limits what is reported for a servo that travels more than 180 degrees:

Case Reported
the ends more than 180 degrees apart, each within 180 degrees of the centre (-100 and +100) both end angles and both errors as they are; the two ends are never subtracted from each other
an end more than 180 degrees from the centre (+200) the end angle 360 degrees off (-160); the angle error is right while the commanded angle names the same position (+200), since it is wrapped
a move that ends within 2.0 degrees of a whole turn from its start unmoved
the direction of a move, and the turns of a winch servo not judged, not counted

For each move, from its command to the next command (constants in servo_test.h):

Term Rule
moved the angle leaves SERVO_TEST_ENC_MOVED_DEG, 2.0 degrees, of the angle read before the command, the shortest way round; that reading must be younger than SERVO_TEST_ENC_STALE_MS, 500 ms, or the move is not judged
settled after it has moved, a reading whose still time is at least SERVO_TEST_ENC_HOLD_MS, 100 ms, and whose stillness began after the command. The angle has then stayed within SERVO_TEST_ENC_TOL_COUNTS, 12 counts or 1.05 degrees, of an anchor for that long
travel time (angle) the start of that stillness minus the command: the moment the angle came within the tolerance of its final value
end angle the angle at the last reading before the next command, for a settled move
angle error the mean end angle at an end, taken on the circle from the step's first end angle there, minus that end's commanded angle, wrapped to -180 to +180 degrees
unmoved the angle never left the 2.0 degrees
late it moved and was not still for 100 ms before the next command

The tolerance is the coprocessor's SENSE_ENC_STILL_TOL; test_as5600 holds the two equal. The still time is kept on the coprocessor at its 2 ms sample interval, so the travel time does not depend on how often the panel reads the page (every 40 ms). It starts at the command as the test issues it and so includes the command's way to the pin: the render loop, the control task, the link and the next PWM frame, up to one poll interval and one frame, not measured. It ends when the angle comes within 1.05 degrees of its final value, which is earlier than the servo arm's last movement by the time that takes: on a 0.09 degrees a microsecond servo at 1.2 us a millisecond, about 10 ms. Only counted moves are reported. The moves that place the horn at each end first are not. A move is left out of the angle's counts, neither unmoved nor late, when the angle has a gap while the move is open and the move has not settled (a reading marked invalid, or one that follows readings lost on the way to the screen after a stall of 320 ms or more, either of which drops the angle history), when the move has no start angle, and when the run ends for any reason other than completion (STOP, switch to SAFE, link loss, supply fault, stall) before the move settled: its window was cut short, and the current's results do not count such a move either. A move that had settled before the gap or the abort keeps its result.

The angle is a reading only while the sensor detects its magnet (STATUS MD, Link). While it reports none, its count is not a position: the panel hands it to nothing, the reading reaches the run marked invalid with the reason, the CSV's angle column is empty, and an open move that had not settled is left out as above. The report then has the line No magnet: the AS5600 reported none N time(s). ..., N being the times the sensor went from any other state to "no magnet" during the run, a run started in that state included. A magnet reported too weak or too strong (ML, MH) with MD set leaves the angle in use: the datasheet states no effect on the angle and specifies its noise for 30 to 90 mT only. The report counts those readings: Field: N reading(s) with the magnet too weak, M too strong. .... Neither line is written when its counts are 0.

The report adds a header line (Encoder:), a table per step -- the mean end angle and its error at each end, the mean and longest travel time, the moves counted, unmoved and late -- and the commanded angles with the rules above. The current's table and its Travel column stay, so the two times sit side by side: on the PD mini the current's is an upper bound that lags the horn by about 0.3 s, and the angle's is not. The CSV gains two columns, angle (deg) on every row whose angle reading is younger than 500 ms, and travel angle (ms) on the first row taken at or after the reading that found the settle. Each row takes the newest angle reading taken at or before the row, from the last 16 readings (about 640 ms), so the order in which the panel handles readings and rows does not move an angle onto the wrong row. The report notes that the deadband is not measured: it needs steps smaller than the end-to-end moves the test makes, and the test makes none. The SERVO screen's MEASURED row shows the live angle while AS5600 is on. A link that goes down clears the reading: the row shows dashes and ENC CENTRE sets nothing until a reading arrives with the link back. The same holds while the sensor reports no magnet.

What ends a run

Every ending switches the output off, releases the servo to its centre, and still writes the report, marked ABORTED with the reason. The bench stays ARMED unless the ending was a switch to SAFE, STOP or leaving the screen, which switch the bench to SAFE. A step the run has posted and the panel has not sent when the bench switches to SAFE or stops is not sent. After a run ended by a switch to SAFE, STOP or leaving the screen, the horn and COMMANDED stay at the position the run last drove; after an ending that leaves the bench ARMED they show the rest the release puts the pins at, 1500 us for STANDARD PWM whatever the trim, and the next drag or knob turn starts from it. Once a run is over, whichever screen is up, SUPPLY's set points go back to what they were before it. That waits until the run's OFF has been sent, a reading taken after that in which the supply itself reports the output off, no ON is on its way and OUTPUT ON is not being held on SERVO or SUPPLY. Set points changed after the run ended are left as they are.

Reason in the report Cause
STOP STOP on the band
bench SAFE DISARM, or anything else that switched the bench to SAFE
link lost the link to the coprocessor went down during the run
SERVO screen left another screen opened
stopped by the operator STOP TEST, a finger on the dial, CENTRE, SWEEP, RELEASE, a tap on a set point, PROGRAM
servo settings changed the type, frame rate, pulses, trim, travel, reverse or SPEED changed
touch events lost events went missing between two frames
supply not answering a reading marked not answering
supply tripped the output went off on a trip
supply output went off the output went off otherwise, OUTPUT OFF among them
no new supply reading for 1.5 s SERVO_TEST_STALE_MS
supply output did not come on not on 3000 ms after the ON
set point not read back in 3 s the supply did not take a step's voltage
step above the voltage cap a step above the cap in force: VOLTAGE MAX, or the input voltage of the PD mini less 0.7 V
above STALL AT for 1 s SERVO_TEST_STALL_ABORT_MS
constant current for 1 s the supply reported constant current for SERVO_TEST_CC_ABORT_MS
no INA3221 window for 0.2 s a run on the INA3221: SERVO_TEST_WIN_STALE_MS without a window that holds current and voltage. A pass 199 ms after the last window leaves the run running, one at 200 ms ends it
INA3221 reset itself a run on the INA3221: the part's reset count moved
INA3221 not answering a run on the INA3221: no SENSE read in 200 ms shows the part online and identified on a bus that is not stuck
INA3221 window without current a run on the INA3221: the newest window holds no current samples, or its number has stood for 200 ms
INA3221 set-up not held a run on the INA3221: the coprocessor no longer holds the set-up, or SETUP has the INA3221 off
INA3221 no longer the meter a run on the INA3221: the meter changed and the panel did not name the condition

The six reasons of a run on the INA3221 are the conditions under which the INA3221 is the rail's meter. The supply's reasons hold on either meter: its state is read in every run.

A step is never asked above the cap: a run whose steps lie outside the supply's range is refused at START, and a cap that comes down during a run ends it before the step above it.

Verdict

Over the voltage steps (the brown-out walk is reported, not judged), FAIL when one of these holds:

  • the highest idle current is above IDLE CURRENT;
  • the highest holding current is above HOLD CURRENT;
  • the longest travel time is above TRAVEL TIME, where the current's meter times travel (not the PD mini, and not the INA3221's windows);
  • a reading after SETTLE is above STALL AT;
  • a counted move was late: movement seen, no arrival within the window, 3000 ms plus the meter's lag.

Otherwise NOT MEASURABLE when a counted move was unseen, or when the brown-out walk saw no movement at its first voltage, and PASS when neither holds. A run of the brown-out walk alone that sees nothing reads NOT MEASURABLE, not PASS. Its Result line then reads no movement seen at 5.00 V, the brown-out walk's first voltage, and Brown-out start under the limits gives the same voltage with NOT MEASURABLE. NOT MEASURABLE says the current could not show every move: a servo moving under the threshold and one standing still read alike. The report's Result line gives how many of the counted moves showed no movement, and Moves seen how many were unseen. A servo that does not move reads NOT MEASURABLE, not FAIL. With no move arrived there is no longest travel time, and the Travel time line reads longest -- and not measured, no move arrived, on any meter.

A LIMITS value of 0 is not checked; STALL AT always is. A current is compared by its magnitude and in whole mA: see Stall and constant current.

Files

A run takes the next run number on the card, as a bench in ARMED does, and the SD card's own task writes its files: BENCHnnn.CSV, one row per reading of the run's meter, and with the DUT page's REPORT on, BENCHnnn.TXT. A run is one CSV: the run log of a bench in ARMED writes no row while a run is under way. Its time column steps over the run and its rows start again when the run ends. A number carried by a BENCHnnn.TXT alone, its CSV deleted on a computer, is taken all the same, so no report is overwritten, and the log viewer's DELETE on a run removes its report with it. A run the card cannot take says so on the band and on the result, NOT RECORDED. Rows the queue to the card had no room for are counted in the report. From the run's start until the card has closed its CSV and its report, the run counts as an open log run, the time between the file's OPEN and its answer included: Wi-Fi and an update wait for it, and the log viewer neither lists nor opens the file still being written.

The CSV, semicolon-separated with a decimal point, as every log the bench writes:

Column Unit What it is
time (s) s when the panel had the reading, from the run's start
test STEP or BROWN-OUT
step the step, 1 to n in the order run
phase SET, SETTLE, IDLE, MOVE or HOLD
command (us) us the pulse commanded
position (us) us the measured position; empty, as nothing measures it
set (V) V the step's voltage
voltage (V) V the meter's: at the supply's output, or CH1's mean bus voltage in the window
limit (A) A the current limit
current (A) A the meter's, signed: the supply's reading, or the window's mean
power (W) W voltage times current
mode the supply's: CV, CC or OFF. On the INA3221 the mode of the supply's last reading, empty before the first
travel (ms) ms on an arrival's row: that move's travel time
angle (deg) deg with AS5600 on only: the horn's angle from the centre count, from the newest reading taken at or before the row; empty when that reading is older than 500 ms or there is none
travel angle (ms) ms with AS5600 on only: on the row after a move settled, its travel time from the angle
meter INA3221, PDMINI or MODEL, on every row
window on the INA3221: the window's number, modulo 65536; a step of more than 1 is windows that never reached the run
current max (A) A on the INA3221: the window's highest 1 ms sample
current min (A) A on the INA3221: its lowest
voltage min (V) V on the INA3221: the lowest bus voltage sample in the window
clipped on the INA3221: samples in the window at an end of the range, held at 255

The last six columns follow whatever is before them: columns 14 to 19 without AS5600, 16 to 21 with it. On the PD mini and the model the five after meter are empty. A file written before these columns, 13 wide or 15 with AS5600, reads in the log viewer as before: its parser takes the columns from the header row.

The report from the host suite's replay of an MG90S micro servo's run on the bench with the PD mini (test/host/fixtures/servo-mg90s.csv), with TRAVEL TIME set to 800 ms:

RCBENCH SERVO TEST REPORT
Result:         PASS
Device:         MG90S
Firmware:       rcbench 0.20.0
Log:            the .CSV with this file's number, one row per supply reading
Supply:         PD mini
Current:        PD mini
Voltage:        PD mini
Readings:       9.1 /s taken by the supply, 9.1 /s reached the test
Skipped:        0 readings the supply took never reached the test
Resolution:     one reading every 109 ms: a travel time is late by up to that
Lag:            about 300 ms from a change of current to the reading that shows it
Repeats:        a reading can repeat the last value for several readings
Travel times:   an upper bound, not checked against the limit
Const. current: 0 supply readings, longest stretch 0 ms
Duration:       184.0 s
Log rows:       1684 written, 0 lost to a full queue

SETTINGS IN FORCE
Type:           STANDARD PWM, centre 1500 us, 1000-2000 us, trim +0 us, reverse OFF
Frame rate:     50 Hz
Can destroy:    none in force
HV servo:       OFF, no step above 6.0 V
Ends:           1100 us and 1900 us (RANGE 80 % of TRAVEL +/-90 deg)
Steps:          4.80 V 6.00 V
Brown-out:      from 5.00 V down in 0.20 V steps to 3.00 V
Current limit:  2.00 A
Timing:         settle 500 ms, idle 1000 ms, dwell 200 ms (hold measured 600 ms)
Length:         60 s a step
Limits:         idle OFF, holding OFF, travel 800 ms, stall 2.00 A

RESULTS PER STEP (currents in A, times in ms)
Set V  Meas V  V min  Idle   Thresh Moving Peak   Hold lo Hold hi Travel Longest Moves Late Unseen
 4.80    4.80  4.80   0.004  0.020  0.037  0.065  0.001   0.001   861    989        41    0      0
 6.00    6.00  5.99   0.001  0.020  0.040  0.077  0.001   0.001   892    978        41    0      0
Thresh: movement is a reading max(0.020 A, 3 x idle noise) from the level before the command.
Arrival: after a reading Thresh above the end's holding level, the first back within 0.05 A of it.
Late: moves seen moving that did not arrive within 3300 ms.
Unseen: moves with no movement seen; not timed, not counted late.

BROWN-OUT
Moved at every step down to 3.00 V; lower not tested.
No movement: no reading of a move more than Thresh, 0.023 A at 3.00 V, from the level before it.

AGAINST THE LIMITS PAGE
Idle current     highest 0.004 A, limit OFF: not checked
Holding current  highest 0.001 A, limit OFF: not checked
Travel time      longest 989 ms, limit 800 ms: upper bound, not checked against the limit
Stall threshold  highest 0.077 A, STALL AT 2.00 A: PASS
STALL AT 2.00 A cannot be reached: current limit 2.00 A
Moves arrived    0 late: PASS
Moves seen       0 unseen: PASS
Brown-out start  movement seen at 5.00 V: PASS

NOT MEASURED
Position: nothing measures the horn; every result is the supply's current.
Current peaks between two readings: the supply reports one value a reading.
The command's way from the panel to the pin, inside every travel time.

Every move is seen at the 0.020 A threshold and arrives; the brown-out walk replays the 5.00 V response at every voltage, so it says nothing about this servo below 5.00 V. The same replay of a 1102HB digital servo, which holds 0.015 to 0.029 A and peaks at 0.039 to 0.044 A, reads:

Result:         NOT MEASURABLE - 25 of 46 counted moves showed no movement in the current
...
Set V  Meas V  V min  Idle   Thresh Moving Peak   Hold lo Hold hi Travel Longest Moves Late Unseen
 4.80    4.80  4.79   0.015  0.020  0.025  0.037  0.028   0.015   687    772        22    0     13
 6.00    5.99  5.99   0.003  0.020  0.027  0.042  0.029   0.017   636    688        24    0     12
...
No movement seen at 5.00 V, the first step: not measurable.

Its moves to the high end leave the low end's 0.028 A and never pass it by 0.020 A: all of them are unseen. Its moves to the low end are seen and arrive. On 0.13.0 the same servo read FAIL with all 34 counted moves late.

A run on the INA3221 has these lines in place of the PD mini's, here from the host suite's modelled bench:

Log:            the .CSV with this file's number, one row per INA3221 window
Supply:         PD mini
Current:        INA3221 CH1, shunt 100.0 mOhm, range 1.638 A
Voltage:        INA3221 CH1, load side of the shunt
Shunt:          up to 0.164 V lost across it at the range; the set point is not raised for it
Readings:       20.0 /s windows closed by the INA3221, 20.0 /s reached the test
Skipped:        0 windows the INA3221 closed never reached the test
Resolution:     one window every 50 ms: a travel time is late by up to two windows and the poll that reads them
Lag:            about 50 ms from a change of current to the reading that shows it
Travel times:   an upper bound, not checked against the limit
...
Position: nothing measures the horn; every result is the INA3221's current on CH1.
Current between two 1 ms samples of CH1: a window holds their mean, highest and lowest.

An aborted run reads Result: ABORTED - <reason>, and a step it cut short is marked (cut short); one it never reached reads not run. Can destroy names the red tag when a heli type or a frame rate above 60 Hz is in force. Every word of the report is in one table in shared/servo/servo_report.c, and the report is written in the interface language showing when its run starts: German from shared/ui/ui_text_de.c (Interface language). The CSV is English in every language.

What is not measured

Three runs of 0.13.0 on the bench with the PD mini, from a tester: an MG90S micro servo, a 1102HB digital and an MS24 digital. The MS24, moving at 0.16 to 0.18 A, passed. The MG90S and the 1102HB read FAIL, every move late, because 0.13.0 took movement to be 0.10 A; both servos moved. The host suite replays the MG90S's and the 1102HB's CSVs (test/host/fixtures/, trimmed) against the engine, and an MS24-like case, the MG90S's currents times 3. The host suite holds the engine to servo_sim and supply_sim, the SERVO screen driving it, and the CSV read back by the log viewer's parser. Not measured: the PD mini's averaging, and the command's delay to the pin.

test_servo_test_win runs the test on the INA3221 as meter on the host: the modelled INA3221 carries servo_sim's current, the coprocessor's schedule and pages turn it into windows, sense_link takes each once and servo_source names the meter, beside a model of the PD mini read every 104 ms. Two recordings from a bench on 0.14.0 are replayed: an MS24's whole CSV on the PD mini (servo-ms24-pdmini.csv), with its two spells of constant current, and the bench log written beside it (servo-ms24-windows.csv), which holds 1309 of the 3817 windows the INA3221 closed and ends a run on the INA3221 at its first gap of more than 200 ms: window 19804 is followed by 20409, 30.25 s later. The run reads 50 windows and counts the 5 window numbers missing before that gap as skipped. Not measured on a bench: a window's lag behind the horn, whether the 50 ms mean shows the moves of a servo that the PD mini does not, what CH1 reads with a servo on a stop, and the constant-current rule against a PD mini.

The commanded position follows ARMED

The SERVO screen's commanded position changes only while the bench is ARMED, which is while a pin follows it.

Bench Commanded position
SAFE the position last driven; the dial, the rotary knob, CENTRE and SWEEP are refused and nothing is sent
at the switch to ARMED the surface's rest: the midpoint of the channel's endpoints, without TRIM
ARMED what the dial, the knob, CENTRE, a sweep or a run commands
TYPE Endpoints Value at the switch to ARMED
STANDARD PWM 1000 to 2000 us 1500 us
NARROW 760 660 to 860 us 760 us
WIDE 800 to 2200 us 1500 us
HELI CYCLIC 820 to 2220 us 1520 us

The rest is outputs_role_rest() in shared/outputs/outputs.c, the value the coprocessor renders on a channel in ARMED that nobody commands, put through the range the screen's commands carry. That range is centred on PULSE CENTRE, so a PULSE CENTRE set off the middle of PULSE MIN and MAX is the value at the switch to ARMED. TRIM moves commanded positions and not the rest: with TRIM +20 the switch to ARMED shows 1500 us and a position at 0 deg is 1520 us.

A sweep ends at a switch to SAFE and its last drawn position stays on screen; no position of it is sent after the switch to SAFE. The controls, one by one: Screens.

The panel centres the surfaces before it switches to ARMED and the screen shows the rest when the bench reports ARMED; the time between the two on a bench is not measured.

Sweep and SPEED

SWEEP on the SERVO screen drives the servo through the TEST page's curve. SPEED on the right card limits how fast the output may move. When SPEED is slower than the fastest change the curve asks for, SPEED shapes the motion instead of the curve, and SPEED's row reads SPEED LIMITS THE SWEEP in the warning colour (Screens).

The fastest change, with f the TEST page's rate in Hz and A the amplitude in degrees (RANGE of the travel either side of PULSE CENTRE):

CURVE Fastest change Where
square a jump at each change of end
sine 2 pi f A through the centre
triangle 4 f A throughout

SPEED below 100 % allows 3.6 deg/s per percent: 36 deg/s at 10 %, 356.4 deg/s at 99 %. At 100 % the command is not slewed and nothing is limited. A square is limited at every SPEED below 100 %. The dwell does not enter: it adds time at the ends, not to the motion. The line follows the settings, before SWEEP is pressed and while it runs. sweep_slew_limited() in shared/servo/servo_sweep.c decides it, in the command units the coprocessor slews in.

TEST page A Fastest change Clears at SPEED
sine, 0.5 Hz, RANGE 80 %, TRAVEL +/-90 deg 72 deg 226 deg/s 63 %
triangle, 0.5 Hz, RANGE 80 %, TRAVEL +/-90 deg 72 deg 144 deg/s 40 %
square, any any a jump 100 %

To clear the line, raise SPEED, or lower the TEST page's SPEED (the rate) or RANGE.

The line compares the curve with SPEED only. A servo slower than both limits the sweep as well; nothing on the bench measures the horn, so that is not shown.

PAUSE, the sweep button while a sweep runs, holds the output where it has got to, and the button reads PAUSED, filled in the warning colour. A tap on PAUSED carries the sweep on from the phase it was paused at, on a coprocessor speaking protocol 4.6; an older one starts the curve over. A paused sweep is the moment to raise SPEED: the pause stays, and the resume runs at the new rate.

Prerequisites

Current sensing on the servo rail. The limit search reads INA3221 CH1, wired and enabled in SETUP INTERFACES, and nothing else. The synchroniser needs a sensor across the pair of outputs, which is not fitted. The automatic test reads the INA3221 or the PD mini, or runs on the panel's supply model. Programming LEFT ANGLE and RIGHT ANGLE needs the programming port (Servo programmer).

The pulses themselves exist: the coprocessor's PWM (pulse-width modulation) driver is written, and DShot and the output drivers describes it. The order of work is in STATUS.md.