Automatic Needle Valve Controller - ISISComputingGroup/ibex_developers_manual GitHub Wiki

Introduction

This is controlling the flow of helium in a cryostat, via a needle valve, based on a lookup table implemented in the hardware.

The underlying hardware is a Eurotherm controller in MODBUS communications mode (see here to change), and automaticNeedleValve.db adds some extra settings on top. This controller uses the 'Automatic Needle Valve Controller' OPI in IBEX.

The needle valve operation revolves around two modes: manager mode and setpoint mode.

The latter has the two modes 'Automatic' and 'Manual', which dictate the behaviour of the needle valve:

  • Automatic mode:
    • Temperature (TEMP) is writable and readable
    • Flow (MANUAL_FLOW) can only be read
  • Manual mode:
    • Flow (MANUAL_FLOW) is writable and readable
    • Temperature (TEMP) can only be read

Note: the above assumes manager mode is enabled; items are only writable in manager mode.

Main records

automaticNeedleValve.db

PV Description Access
FLOW "Flow" Flow readback from transducer Read only
VALVE_DIR Valve Direction; 0 = Closing, 1 = Opening Read only
FLOW_SP_MODE_SELECT Flow Setpoint Select; 0 = Auto setpoint mode, 1 = Manual setpoint control Read/Write
MANUAL_FLOW Manual flow setpoint; Reliant on FLOW_SP_MODE_SELECT being at 1 (i.e. Manual) Read/Write
FLOW_SP_LOWLIM Low setpoint limit for flow control Read/Write
NEEDLE_VALVE_STOP Ability to 'inhibit' Loop 2 Read/Write

Other

PV Description Access
TEMP Temperature readback from Eurotherm Read/Write

Access control architecture

There are two mechanisms at work controlling SP access rights here; setpoint mode and manager mode.

Manager mode

All setpoint PVs have the field field(ASG, "MANAGER"), so all writable items are only accessible when manager mode is enabled (e.g., $(P)CS:MANAGER=1).

Setpoint mode

As detailed above, the access rights to the PVs MANUAL_FLOW and TEMP are also controlled via setpoint mode.

These rights are managed via a series of fanout/seq records, which set 0 or 1 to the .DISP field (see EPICS: Fields Common to All Record Types) of each of these PVs, depending on the mode:

Auto Manual
Flow .DISP=1 .DISP=0
Temperature .DISP=0 .DISP=1

See below for an explicit summary of the write access of these two PVs under both modes.

MANUAL_FLOW

FLOW_SP_MODE_SELECT=0 (Auto) FLOW_SP_MODE_SELECT=1 (Manual)
CS:MANAGER=0 (Off) Read only Read only
CS:MANAGER=1 (On) Read only Readable & Writable

TEMP

FLOW_SP_MODE_SELECT=0 (Auto) FLOW_SP_MODE_SELECT=1 (Manual)
CS:MANAGER=0 (Off) Read only Read only
CS:MANAGER=1 (On) Readable & Writable Readable only

The use of cainfo may be useful for troubleshooting to check read/write permissions.