PH_meter_self checking - jimaobian/DFRobotWiki GitHub Wiki
This part will tell you how to check whether you get a fault ph meter. note: it is only suitable for V1.
- Make sure the power supply is standard 5.0V (Some computer can't provide enough power supply with 5V, generally it will be 4.8V or 4.9V)
- Power the ph convert board, follow the picture and measure the voltage of two capacitances. It should be close to 5V. (purple)
3.Short current the BNC connector, like what I did in the photo. If you have a multimeter, measure its analog pin, it should be 2V. If you don't have multimeter. Connect the adapter to Arduino board, run the sample code. it should output PH:7 in the serial monitor.
4.If everything goes well. It should work well. But don't forget to calibration. Note:
- Please keep PH convert board clear, and leave it far away from the water. It is not a wateproof device.
- It is a chemical device, the output value will exist some delay time when you plug it in the solution. pleas wait 30s. waiting its stable state.
- Random value: please check the BNC connector, when the connector is not well, it will output random signal.