LCN Binding - jfederico/openhab GitHub Wiki
Author: Tobias Jüttner, Date: 10/28/2015
Overview
1. LCN Quick-Reference
1.1 LCN Modules
Active LCN components connected to the LCN bus are called LCN modules. LCN modules are addressed by their numeric id: Valid range is 5..254
In larger buildings, a second topologic layer is added: segments. Valid range is 5..128 or 0 (= no segments exist) or 3 (= target all segments)
Examples: S000M005, S011M100
LCN modules within the same segment can be grouped: Valid range is 5..254 or 3 (= target all groups)
Examples: S000G022, S011G111
1.2 LCN Firmware Versions
Each LCN module has a feature-set based on its firmware version. This version is written as follows: [year since 1990][month][day]
Each component is written in hexadecimal with 2 characters. Examples:
- 090101 = 1. january 1990
- 0D0C01 = 1. december 2003
- 170206 = 6. feb. 2013
1.3 LCN Output-Ports
LCN modules support 2 to 4 analog output-ports (number depends on firmware version). Status values are always in percent.
Modules since 170206 have a 0.5%-steps resolution. Older modules have a 2%-steps resolution.
The time it takes the output-port to reach its set-point is called ramp.
1.4 LCN Variables
LCN modules support:
- 3 or 12 (since 170206) analog variables for general usage
- 2 regulator set-points
- 5 or 4x4 (since 170206) thresholds (trigger levels)
- 4 S0-input counters (LCN-BU4L must be connected)
1.5 LCN Regulators (additions to variables)
LCN modules have 2 regulators. Each one has a set-point and uses one variable as its value-source (see LCN Variables).
1.6 LCN Relays
LCN modules support up to 8 relays. If no hardware-relays are connected, the relays can still be used as virtual.
1.7 LCN Binary-Sensors
LCN modules support up to 8 binary-sensors (hardware periphery must be connected).
1.8 LCN LEDs (legacy name: lamps)
12x multi-state variables used for logic operations.
Values: 0(OFF), 1(ON), 2(BLINK), 3(FLICKER)
1.9 LCN Logic-Operations (legacy name: sums)
4x multi-state variables representing the result of associated LEDs.
Values: 0(NOT), 1(OR), 2(AND)
1.10 LCN Keys
LCN keys are data-points with bound commands. LCN modules support 3 ("A-C") or 4 ("A-D") key-tables (number depends on firmware version).
Each key-table holds 8 keys. Examples: A1, A7, D8
Each key has 3 command types: HIT(press), MAKE(long press), BREAK(long press release)
Some of these keys can be locked which means the bound (LCN-)commands cannot be executed (via LCN)!
2. Configuration Guide
The openHAB LCN binding connects to one or more LCN-PCHK instances via TCP/IP. This means 1 unused LCN-PCHK license is required!
The minimum recommended version is LCN-PCHK 2.8 (older versions will also work, but lack some functionality). Visit http://www.lcn.de for updates.
2.1 Example configuration for a connection
lcn:id1=myhome
lcn:address1=localhost:4114
lcn:username1=lcn
lcn:password1=test123
lcn:mode1=native200
This defines a connnection (#1) to LCN-PCHK on localhost port 4114. myhome will be the connection's unique identifier (connid, used in openHAB mapping-definitions). address can be any IP or host name. The port (:4114) is optional.
mode specifies the operation mode of the LCN bus:
- LCN busses with solely modules with firmware 170206 (feb. 2013) or newer use
native200
(means: output-ports have 200 dimming steps) - All other LCN busses use
native50
(means: output-ports have 50 dimming steps)
This is an important setting as the operation mode is programmed into the LCN modules by LCN-PRO. If you experience unexpected behavior while dimming output-ports, the connection is probably in the wrong operation mode!
For older versions than LCN-PCHK 2.8: Use percent50
and percent200
instead (loses some precision).
2.2 Adding a second connection (#2)
lcn:id2=myotherhome
lcn:address2=...
...
More connections are defined by incrementing the appended counter (2
in the example).
Do not skip any numbers! GOOD: 1,2,3,4 BAD: 1,3,4
2.3 Advanced settings
lcn:timeout1=2000
<- Timeout for requests in milliseconds (default = 3500
)
3 Items Configuration Guide
LCN items are defined by mapping openHAB commands to LCN commands:
Example item with 2 mappings:
Switch exampleItem "my text" {lcn="[openHABcmd:connid:lcncmd...], [openHABcmd:connid:lcncmd...], ..."}
- openHABcmd: ON, OFF, INCREASE, DECREASE... (must be replaced when using the examples)
- connid: Unique identifier for the LCN connection. Always
myhome
in the examples here - lcncmd...: What to do
Everything is case-insensitive.
Visualization of an item is done as follows:
- With an explicit visualization mapping ("best practice")
- or implicitly by analyzing all present mappings ("lazy")
A visualization-mapping should always be the first one specified (before all others)!
The benefits of an explicit visualization mapping: By explicitly telling the openHAB item where to get the current status from, it is possible to visualize one thing, but control something completely different!
3.1 LCN Addresses
Examples for S000M005:
openHABcmd:connid:S0.M5...
openHABcmd:connid:0.5... ("M" is implicit if missing)
openHABcmd:connid:0.M005...
Examples for S000G011:
openHABcmd:connid:0.G11...
openHABcmd:connid:S0.G11...
3.2 LCN Output-Ports
Switch S000M005, output-port 2 (no ramp):
Switch exampleO2 "M005 output-port 2" {lcn="[myhome:OUTPUT_STATUS.0.5.2], [ON:myhome:ON.0.5.2], [OFF:myhome:OFF.0.5.2]"}
The same using lazy visualization and ramp 10s:
Switch exampleO2 "M005 output-port 2" {lcn="[ON:myhome:ON.0.5.2.10s], [OFF:myhome:OFF.0.5.2.10s]"}
Visualize S000M005, output-port 3 current value (percent):
Number exampleO3 "M005 output-port 3 [%d]" {lcn="[myhome:OUTPUT_STATUS.0.5.3]"}
Relative output-port commands:
- +10.5% output-port 2:
[openHABcmd:myhome:ADD.0.5.2.10,5%]
- -5% output-port 2:
[openHABcmd:myhome:SUB.0.5.2.5%]
- alternative for -5%:
[openHABcmd:myhome:REL.0.5.2.-5%]
Dimmer S000M005, output-port 2 (5% steps):
Dimmer exampleO2 "M005 output-port 2 [%s]" {lcn="[myhome:OUTPUT_STATUS.0.5.2], [INCREASE:myhome:ADD.0.5.2.5%], [DECREASE:myhome:SUB.0.5.2.5%], [%i:myhome:DIM.0.5.2.%i]"}
"%i"-mapping is required for HABDroid
Toggle S000M005, output-port 2: [openHABcmd:myhome:TOGGLE.0.5.2]
with ramp 10s: [openHABcmd:myhome:TOGGLE.0.5.2.10s] (also valid: 0,5s,1second,10seconds,30sec)
Dim S000M005, output-port 2 to 66,5%: [openHABcmd:myhome:DIM.0.5.66,5%]
with ramp 10s: [openHABcmd:myhome:DIM.0.5.2.66,5%.10s]
Note: ON
/OFF
/DIM
/TOGGLE
also support "all outputs an once": Replace the output-port (1,2,3,4) with ALL
.
The only allowed unit for ramps is seconds!
3.3 LCN Variables
Variables can be shown and changed using several measurement units:
lcn
(internal native/raw format)°C
/°Celsius
/Celsius
°K
/°Kelvin
/Kelvin
°F
/°Fahrenheit
/Fahrenheit
lx
/Lux
(for periphery connected to the LCN module's I-port)lx_T
/Lux_T
(for periphery connected to the LCN module's T-port)m/s
%
/Percent
(used for humidity)ppm
(used for CO2)V
/VOLT
A
/Amp
/Ampere
°
(angle) /Degree
All these alternative spellings can be used.
Visualize S000M0005, Var 2/12:
String exampleVar2 "M005 Var 2 temperature [%s °C]" {lcn="[myhome:VAR_VALUE.0.5.2.°C]"}
String exampleVar2 "M005 Var 2 [%s]" {lcn="[myhome:VAR_VALUE.0.5.2]"}
Visualize S000M0005, Regulator 1 Set-Point:
String exampleSetPoint1 "M005 regulator 1 set-point [%s °C]" {lcn="[myhome:SETPOINT_VALUE.0.5.1.°C]"}
Set-point control to change regulator 1:
Number exampleSetPoint "M005 regulator 1 set-point [%f °C]" {lcn="[myhome:SETPOINT_VALUE.0.5.1.°C], [%i:myhome:SETPOINT.0.5.1.%i°C]"}
Number exampleSetPoint "M005 regulator 1 set-point [%f °C]" {lcn="[%i:myhome:SETPOINT.0.5.1.%i°C]"} <- Short form
Visualize S000M0005, threshold 3-4 (register is 3!):
String exampleT34 "M005 threshold 3-4 [%s °C]" {lcn="[myhome:THRESHOLD_VALUE.0.5.3.4.°C]"}
Visualize S000M0005, S0-input 3/4 (requires LCN-BU4L connected to the LCN module):
String exampleS0 "M005 S0-input 3 [%s]" {lcn="[myhome:S0_VALUE.0.5.3]"}
3.4 Changing Variables
Example S000M005, variable 7:
- Add 10°C:
[openHABcmd:myhome:VAR_ADD.0.5.7.10°C]
- Sub 10°C:
[openHABcmd:myhome:VAR_SUB.0.5.7.10°C]
or[openHABcmd:myhome:VAR_REL.0.5.7.-10°C]
- Add raw value 15:
[openHABcmd:myhome:VAR_ADD.0.5.7.15]
or[openHABcmd:myhome:VAR_ADD.0.5.7.15LCN]
- Reset to 0:
[openHABcmd:myhome:VAR_RESET.0.5.7]
- Set to 10°C:
[openHABcmd:myhome:VAR.0.5.7.10°C]
Example S000M005, set-point regulator 2
- Add 1°C:
[openHABcmd:myhome:SETPOINT_ADD.0.5.2.1°C]
- Reset to 0:
[openHABcmd:myhome:SETPOINT_RESET.0.5.2]
- Set to 10°C:
[openHABcmd:myhome:SETPOINT.0.5.2.10°C]
Example S000M005, threshold 3-4 (register is 3!):
- Add 10,5°C:
[openHABcmd:myhome:THRESHOLD_ADD.0.5.3.4.10,5°C]
3.4.1 Special Cases
VAR
andVAR_RESET
with modules before 170206: If the command's target is an LCN group, those older modules require special commands to work:VAR_OLD
,VAR_RESET_OLD
- Thresholds with modules before 170206: Older modules only have threshold register 1 (but 5 instead of 4 values!). If the command's target is an LCN group, those older modules require special commands to work:
THRESHOLD_ADD_OLD
,THRESHOLD_SUB_OLD
,THRESHOLD_REL_OLD
3.5 LCN Regulators (additions to variables)
Lock/unlock S000M005, Regulator 1/2:
Switch exampleLockReg2 "M005 reg.2 lock/unlock" {lcn="[ON:myhome:LOCK_REGULATOR.0.5.1], [OFF:myhome:UNLOCK_REGULATOR.0.5.1]"}
Visualize S000M005, Regulator 2/2 lock-state:
Contact exampleLockReg1 "M005 reg.2 lock-state" {lcn="[myhome:REGULATOR_LOCK_STATE.0.5.2]"}
3.6 LCN Relays
Switch S000M005, relay 6/8:
Switch exampleRelay6 "M005 relay 6" {lcn="[ON:myhome:RELAYS.0.5.-----1--], [OFF:myhome:RELAYS.0.5.-----0--]"}
Visualize S000M005, relay 6:
Contact exampleRelay6 "M005 relay 6/8" {lcn="[myhome:RELAY_STATE.0.5.6]"}
More command examples:
Toggle relay 1, turn OFF relays 5+6, turn ON relays 7: [ON:myhome:RELAY.0.5.T---001-]
3.7 LCN Binary-Sensors
Visualize S000M005, Binary-Sensor 4/8:
Contact exampleWindow "M005 bin.sensor 4" {lcn="[myhome:BINARY_STATE.0.5.4]"}
3.8 LCN LEDs (legacy name: lamps)
Visualize S000M005, LED 8/12 numeric state:
Number exampleLed8 "M005 LED 8 [%d]" {lcn="[myhome:LED_STATE.0.5.8]"}
Visualize S000M005 LED 8 text state:
String exampleLed8 "M005 LED 8 [%s]" {lcn="[myhome:LED_STATE.0.5.8]"}
Visualize S000M005 LED 8 state with custom texts:
String exampleLed8 "M005 LED 8 [%s]" {lcn="[myhome:LED_STATE.0.5.8.myOFFtext.myONtext.myBLINKtext.myFLICKERtext]"}
Switch S000M005 LED 8 on/off (lazy visualization):
Switch exampleLed8 "M005 LED 8 on/off" {lcn="[ON:myhome:LED.0.5.8.ON], [OFF:myhome:LED.0.5.8.OFF]}
Switch S000M005 LED 8 blink/flicker (lazy visualization):
Switch exampleLed8 "M005 LED 8 on/off" {lcn="[ON:myhome:LED.0.5.8.FLICKER], [OFF:myhome:LED.0.5.8.BLINK]}
3.9 LCN Logic-Operations (legacy name: sums)
Visualize S000M005 logic-op. 3 numeric state:
Number exampleOp3 "M005 logic-op. 3 [%d]" {lcn="[myhome:LOGICOP_STATE.0.5.3]"}
Visualize S000M005 logic-op. 3 text state:
String exampleOp3 "M005 logic-op. 3 [%s]" {lcn="[myhome:LOGICOP_STATE.0.5.3]"}
Visualize S000M005 logic-op. 3 state with custom texts:
String exampleOp3 "M005 logic-op. 3 [%s]" {lcn="[myhome:LOGICOP_STATE.0.5.3.myNOTtext.myORtext.myANDtext]"}
3.10 LCN Keys
Sending keys (a.k.a. execute bound commands):
Example: S000M005, keys A1,A5,D8
- "hit":
[openHABcmd:myhome:KEYS.0.5.A1A5D8]
or[openHABcmd:myhome:KEYS.0.5.A1A5D8.HIT]
- "make":
[openHABcmd:myhome:KEYS.0.5.A1A5D8.MAKE]
- "break":
[openHABcmd:myhome:KEYS.0.5.A1A5D8.BREAK]
Sending keys deferred/delayed:
Example: S000M005, keys A1,A5,D8
- "hit" in 10s:
[openHABcmd:myhome:KEYS.0.5.A1A5D8.10s]
(range 1..60, also valid:1second
,10seconds
,30sec
) - "hit" in 10m:
[openHABcmd:myhome:KEYS.0.5.A1A5D8.10m]
(range 1..90, also valid:1minute
,10minutes
,45min
) - "hit" in 1h:
[openHABcmd:myhome:KEYS.0.5.A1A5D8.HIT.1h]
(range 1..50, also valid:1hour
,24hours
) - "hit" in 7d:
[openHABcmd:myhome:KEYS.0.5.A1A5D8.HIT.7d]
(range 1..45, also valid:1day
,7days
)
"make"/"break" is NOT supported!
Change lock-state S000M005 lock C1, unlock C2, toggle C7:
[openHABcmd:myhome:LOCK.0.5.C.10----T-]
Switch S000M005, show lock-state of key C4, control lock-state of C4,C5,C5:
Switch exampleC456 "M005 C4(,C5,C6) lock" {lcn="[myhome:LOCK_STATE.0.5.C4], [ON:myhome:LOCK.0.5.C.---111--], [OFF:myhome:LOCK.0.5.C.---000--]"}
The same using lazy visualization (will visualize C4, as it is the first key in the list):
Switch exampleC456 "M005 C4 lock" {lcn="[ON:myhome:LOCK.0.5.C.---111--], [OFF:myhome:LOCK.0.5.C.---000--]"}
Lock keys A1,A2,A3 for 10m: [openHABcmd:myhome:LOCK.0.5.A1A2A3.10m]
Same time-values as KEYS
command.
Only table A is supported!
3.11 Misc Commands
Dynamic text for LCN-GTxD displays (support 4 independent text rows):
Example: S000M005 row 1/4:
[openHABcmd:myhome:DYNTEXT.0.5.1.text up to 60 characters]
The text will be encoded as UTF-8 which means non-ASCII characters will reduce the total available length.
Other commands can be sent by using the LCN-PCK format.
There will be no implicit lazy visualization for these commands!
Beep S000M005 4 times (must be allowed => LCN-PRO):
- tone 1:
[openHABcmd:myhome:PCK.0.5.PIN4]
(range 1..15) - tone 2:
[openHABcmd:myhome:PCK.0.5.PIS004]
Store current output-port value(s) as light-scene 6/10:
- store output 1:
[openHABcmd:myhome:PCK.0.5.SZS1005]
(range is 0..9) - store output 2:
[openHABcmd:myhome:PCK.0.5.SZS2005]
- store output 3(+4):
[openHABcmd:myhome:PCK.0.5.SZS4005]
Storing multiple outputs at once: 1+2+3(+4): SZS7
, 1+2: SZS3
, 1+3: SZS5
, 2+3: SZS6
Recall light-scene 6/10:
recall output 1: [openHABcmd:myhome:PCK.0.5.SZA1005]
(range is 0..9)
Same as store, just SZAx
instead of SZSx
.
Change light-scene register:
to register 5/10: [openHABcmd:myhome:PCK.0.5.SZW004]
(range is 0..9)
4. LCN Demo
ISSENDORFF KG has a LCN-demo set-up that is reachable via internet.
openhab.cfg
lcn:id1=lcndemo
lcn:address1=access.lcn.de:5225
lcn:username1=lcn
lcn:password1=lcn
lcn:mode1=native200
Items
Contact lcnMotionDetect "Motion detect" {lcn="[lcndemo:BINARY_STATE.0.5.4]"}
Contact lcnRelayVis "Relay" {lcn="[lcndemo:RELAY_STATE.0.5.1]"}
Switch lcnRelay "Relay" {lcn="[ON:lcndemo:RELAYS.0.5.1-------], [OFF:lcndemo:RELAYS.0.5.0-------]"}
Switch lcnLightSwitch "Light" {lcn="[ON:lcndemo:ON.0.5.1.2s], [OFF:lcndemo:OFF.0.5.1.2s]"}
Dimmer lcnLightDimmer "Light [%s]" {lcn="[lcndemo:OUTPUT_STATUS.0.5.1], [INCREASE:lcndemo:ADD.0.5.1.5%], [DECREASE:lcndemo:SUB.0.5.1.5%], [%i:lcndemo:DIM.0.5.1.%i]"}
Number lcnCounter "Counter [%d]" {lcn="[lcndemo:VAR_VALUE.0.5.1]"}
String lcnTemp "Temperature [%s °C]" {lcn="[lcndemo:VAR_VALUE.0.5.2.°C]"}
String lcnSetPoint "Set-point [%s °C]" {lcn="[lcndemo:SETPOINT_VALUE.0.5.1.°C]"}
Number lcnSetPointDim "Set-point (10-23°C) [%f °C]" {lcn="[lcndemo:SETPOINT_VALUE.0.5.1.°C], [%i:lcndemo:SETPOINT.0.5.1.%i°C]"}
String lcnRegulatorTarget "Regulator [%s]" {lcn="[lcndemo:OUTPUT_STATUS.0.5.3]"}
Switch lcnRegulatorLock "Regulator lock" {lcn="[ON:lcndemo:LOCK_REGULATOR.0.5.1], [OFF:lcndemo:UNLOCK_REGULATOR.0.5.1]"}
String lcnBright "Brightness [%s lx]" {lcn="[lcndemo:VAR_VALUE.0.5.3.lx]"}
String lcnCO2 "CO2 [%s ppm]" {lcn="[lcndemo:VAR_VALUE.0.5.4.ppm]"}
String lcnThreshold1 "Threshold 1 [%s °C]" {lcn="[lcndemo:THRESHOLD_VALUE.0.5.1.1.°C]"}
String lcnThreshold2 "Threshold 2 [%s °C]" {lcn="[lcndemo:THRESHOLD_VALUE.0.5.1.2.°C]"}
String lcnThreshold3 "Threshold 3 [%s °C]" {lcn="[lcndemo:THRESHOLD_VALUE.0.5.1.3.°C]"}
String lcnThreshold4 "Threshold 4 [%s °C]" {lcn="[lcndemo:THRESHOLD_VALUE.0.5.1.4.°C]"}
Sitemap
sitemap default label="LCN Demo"
{
Frame label="Coffee" {
Text item=lcnMotionDetect
Text item=lcnRelayVis
Switch item=lcnRelay icon="none"
Switch item=lcnLightSwitch
Slider item=lcnLightDimmer
Text item=lcnCounter
Text item=lcnTemp
Text item=lcnSetPoint
Setpoint item=lcnSetPointDim step=0.5 minValue=10 maxValue=23
Text item=lcnRegulatorTarget
Switch item=lcnRegulatorLock
Text item=lcnBright
Text item=lcnCO2
Text item=lcnThreshold1
Text item=lcnThreshold2
Text item=lcnThreshold3
Text item=lcnThreshold4
}
}
Visualization (through LCN-GVS)
Address: http://access.lcn.de/LCNGVSDemo -> OpenHAB
Direct address: http://access.lcn.de/LCNGVSDemo/control.aspx?ui=coffee&proj=OpenHAB
Login: guest
Password: lcn
5. Examples
All examples use S000M005 or S000G006
5.1 LCN Output-Ports
[myhome:OUTPUT_STATUS.0.5.1]
[openHABcmd:myhome:ON.0.5.1]
[openHABcmd:myhome:ON.0.5.ALL]
[openHABcmd:myhome:OFF.0.5.1]
[openHABcmd:myhome:OFF.0.5.ALL]
[openHABcmd:myhome:TOGGLE.0.5.1]
[openHABcmd:myhome:TOGGLE.0.G6.ALL]
[openHABcmd:myhome:DIM.0.5.1.50%]
[openHABcmd:myhome:DIM.0.5.1.50%.10s]
[openHABcmd:myhome:DIM.0.G6.ALL.50%.10s]
[%i:myhome:DIM.0.5.1.%i]
[openHABcmd:myhome:ADD.0.5.1.10%]
[openHABcmd:myhome:SUB.0.5.1.10,5%]
[openHABcmd:myhome:REL.0.5.1.-10%]
5.2 LCN Variables
Measurement units:
lcn
°C
,°Celsius
,Celsius
°K
,°Kelvin
,Kelvin
°F
,°Fahrenheit
,Fahrenheit
lx
,Lux
,lx_T
,Lux_T
m/s
%
,Percent
ppm
V
,Volt
A
,Amp
,Ampere
°
,Degree
Variables
[myhome:VAR_VALUE.0.5.1]
[myhome:VAR_VALUE.0.5.1.°C]
[myhome:VAR_VALUE.0.5.1.lx]
[openHABcmd:myhome:VAR.0.5.1.10°C]
[openHABcmd:myhome:VAR_OLD.0.5.1.10°C] <- For group-targets before 170206
[openHABcmd:myhome:VAR_ADD.0.5.1.10°C]
[openHABcmd:myhome:VAR_SUB.0.5.1.10,5°C]
[openHABcmd:myhome:VAR_REL.0.5.1.-10°C]
[openHABcmd:myhome:VAR_RESET.0.5.1]
[openHABcmd:myhome:VAR_RESET_OLD.0.5.1] <- For group-targets before 170206
Set-Points
[myhome:SETPOINT_VALUE.0.5.1]
[myhome:SETPOINT_VALUE.0.5.1.°C]
[openHABcmd:myhome:SETPOINT.0.5.1.10°C]
[openHABcmd:myhome:SETPOINT_ADD.0.5.1.10°C]
[openHABcmd:myhome:SETPOINT_SUB.0.5.1.10,5°C]
[openHABcmd:myhome:SETPOINT_REL.0.5.1.-10°C]
[openHABcmd:myhome:SETPOINT_RESET.0.5.1]
[%i:myhome:SETPOINT.0.5.1.%i°C]
Thresholds
[myhome:THRESHOLD_VALUE.0.5.1.1]
[myhome:THRESHOLD_VALUE.0.5.1.1.°C]
[openHABcmd:myhome:THRESHOLD_ADD.0.5.1.1.10°C]
[openHABcmd:myhome:THRESHOLD_SUB.0.5.1.1.10,5°C]
[openHABcmd:myhome:THRESHOLD_REL.0.5.1.1.-10°C]
For group-targets before 170206: THRESHOLD_ADD_OLD
, THRESHOLD_SUB_OLD
, THRESHOLD_REL_OLD
S0-Input
[myhome:S0_VALUE.0.5.1]
5.3 LCN Regulators (additions to variables)
[myhome:REGULATOR_LOCK_STATE.0.5.1]
[openHABcmd:myhome:LOCK_REGULATOR.0.5.1]
[openHABcmd:myhome:UNLOCK_REGULATOR.0.5.1]
5.4 LCN Relays
[myhome:RELAY_STATE.0.5.1]
[openHABcmd:myhome:RELAYS.0.5.-----1--]
[openHABcmd:myhome:RELAYS.0.5.-----0--]
[openHABcmd:myhome:RELAYS.0.G6.----TTTT] <- Toggle
5.5 LCN Binary-Sensors
[myhome:BINARY_STATE.0.5.1]
5.6 LCN LEDs (legacy name: lamps)
[myhome:LED_STATE.0.5.1]
[myhome:LED_STATE.0.5.1.myOFFtext.myONtext.myBLINKtext.myFLICKERtext]
[openHABcmd:myhome:LED.0.5.1.ON]
[openHABcmd:myhome:LED.0.5.8.OFF]
[openHABcmd:myhome:LED.0.5.8.BLINK]
[openHABcmd:myhome:LED.0.5.8.FLICKER]
5.7 LCN Logic-Operations (legacy name: sums)
[myhome:LOGICOP_STATE.0.5.1]
[myhome:LOGICOP_STATE.0.5.1.myNOTtext.myORtext.myANDtext]
5.8 LCN Keys
[openHABcmd:myhome:KEYS.0.5.A1A5D8]
[openHABcmd:myhome:KEYS.0.5.A1A5D8.HIT]
[openHABcmd:myhome:KEYS.0.G6.A1A5D8.MAKE]
[openHABcmd:myhome:KEYS.0.G6.A1A5D8.BREAK]
[openHABcmd:myhome:KEYS.0.5.A1A5D8.10s] (range 1..60, also valid: 1second,10seconds,30sec)
[openHABcmd:myhome:KEYS.0.5.A1A5D8.10m] (range 1..90, also valid: 1minute,10minutes,45min)
[openHABcmd:myhome:KEYS.0.5.A1A5D8.HIT.1h] (range 1..50, also valid: 1hour,24hours)
[openHABcmd:myhome:KEYS.0.5.A1A5D8.HIT.7d] (range 1..45, also valid: 1day,7days)
"make"/"break" is NOT supported!
[myhome:LOCK_STATE.0.5.A1]
[openHABcmd:myhome:LOCK.0.5.A.-10-----]
[openHABcmd:myhome:LOCK.0.5.D.------TT] <- Toggle
[openHABcmd:myhome:LOCK.0.5.A1A2A3.10s]
[openHABcmd:myhome:LOCK.0.5.A1A2A3.10m]
[openHABcmd:myhome:LOCK.0.5.A1A2A3.1h]
[openHABcmd:myhome:LOCK.0.5.A1A2A3.7d]
Only table A is supported!
5.9 Misc Commands
[openHABcmd:myhome:DYNTEXT.0.5.1.text in row 1]
[openHABcmd:myhome:DYNTEXT.0.5.4.text in row 4]