Introduction

The getMinSrc modules are used to determine how much spinning reserve capacity (SRC) is required in the grid at each simulation step. If a getMinSrc module is created, then it needs to follow the description below.

Input Variables

Input variables depend on which getMinSrc module is being used. The input variables will be put into the projectGetMinSrcInputs XML file corresponding to that particular getMinSrc. For example, the input variables for getMinSrc0 will be stored in projectGetMinSrc0Inputs. In this case there is one input.

Functions

getMinSrc

Input variables

SO: a reference to the instance of the SystemsOperations which runs the simulation logic.

calcFuture: A bool value that indicates whether the SRC value desired is the current value (calcFuture = False) or a predicted future value (calcFuture = True).

Operation

getMinSrc must calculate the required SRC based on the required percentage of the load and the wind turbines. When other variable energy sources are implemented, such as solar-PV, then those will need to be taken into account as well. Two local variable must be updated: minSrcToStay and minSrcToSwitch. These are the minimum SRC required if keeping the current combination of diesel generators online and if switching the online combination of diesel generators, respectively. Assigning a higher SRC requirement to switch to a different generator combination can be used to reduce diesel switching.

Modules

The getMinSrc modules included in this software include: